Added support for non-high precision APC UPS devices. Tested with APC UPS 8000XL.
This commit is contained in:
@@ -5,9 +5,10 @@ if ($device['os'] == "apc")
|
||||
$oids = snmp_get($device, "1.3.6.1.4.1.318.1.1.1.2.3.1.0", "-OsqnU", "");
|
||||
if ($debug) { echo($oids."\n"); }
|
||||
|
||||
// Try High-Precision First
|
||||
if ($oids)
|
||||
{
|
||||
echo("APC UPS Battery Charge");
|
||||
echo("APC UPS Battery Charge High Precision");
|
||||
$type = "apc";
|
||||
list($oid,$current) = explode(' ',$oids);
|
||||
|
||||
@@ -22,8 +23,29 @@ if ($device['os'] == "apc")
|
||||
$descr = "Battery Charge";
|
||||
|
||||
discover_sensor($valid['sensor'], 'charge', $device, $current_oid, $index, $sensorType, $descr, $precision, '1', $lowlimit, $warnlimit, NULL, $limit , $current_val);
|
||||
}
|
||||
} else { // Try to just get capacity
|
||||
$oids = snmp_get($device, "1.3.6.1.4.1.318.1.1.1.2.2.1.0", "-OsqnU", "");
|
||||
if ($debug) { echo($oids."\n"); }
|
||||
|
||||
if ($oids)
|
||||
{
|
||||
echo("APC UPS Battery Charge");
|
||||
$type = "apc";
|
||||
list($oid,$current) = explode(' ',$oids);
|
||||
|
||||
$precision = 1;
|
||||
$sensorType = "apc";
|
||||
$current_oid = "1.3.6.1.4.1.318.1.1.1.2.2.1.0";
|
||||
$index = 0;
|
||||
$current_val = $current;
|
||||
$limit = 100;
|
||||
$lowlimit = 0;
|
||||
$warnlimit = 10;
|
||||
$descr = "Battery Charge";
|
||||
|
||||
discover_sensor($valid['sensor'], 'charge', $device, $current_oid, $index, $sensorType, $descr, $precision, '1', $lowlimit, $warnlimit, NULL, $limit , $current_val);
|
||||
}
|
||||
}
|
||||
}
|
||||
|
||||
?>
|
||||
|
||||